Circutor AFQ Series User Manual Page 93

  • Download
  • Add to my manuals
  • Print
  • Page
    / 106
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 92
AFQ-4W
Instruction Manual 93
ACTIVE FILTER IN ALARM STATUS
Table 13 shows the messages that might appear on the main screen when the
AFQ-4W is in an alarm status.
ALARM
NTC1 temperature
Description
NTC probe overtemperature.
Corrective
Action
Make sure
that the fans or turbines at the top of the cabinet are
operating properly.
NTC2 temperature
Description
NTC probe overheating
Corrective
Action
Make sure that the fans or turbines at the top of the cabinet are
operating properly.
Inductor Temperature
Description
Inductor overtemperature
Corrective
Action
Ensure that the fans at the bottom of the cabinet are operating
properly.
MAX. DC bus voltage.
Description
The voltage on the DC bus capacitors is too high.
Corrective
Action
Check the unit connections and the input voltages.
MAX. Bus positive voltage
Description
The voltage on the DC bus capacitors is too high.
Corrective
Action
Check the unit connections and the input voltages.
MAX. Bus negative voltage
Description
The voltage on the DC bus capacitors is too high.
Corrective
Action
Check the unit connections and the input voltages.
MAX. Current
Description The AFQ-4W current is too high.
Page view 92