Circutor AFQ Series User Manual Page 61

  • Download
  • Add to my manuals
  • Print
  • Page
    / 106
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 60
AFQ-4W
Instruction Manual 61
The RS-485 connection is shown in Figure 63:
Figure 63: RS-485 connection.
The Modbus configuration of the AFQ-4W is shown in Table 8:
Variable
Value
Protocol
MODBUS RTU slave
Peripheral no.
2
Baud Rate
9600
Parity
No
Data bits
8
Stop bits
1
Table 8: Modbus configuration.
The permitted Modbus functions are (Table 9):
Permitted Modbus functions
(1)
Read (R)
03
Write (W)
10
(1)
Values expressed as hexadecimals
Table 9: Permitted Modbus functions