5�21�-COSφALARM
Inthispointthelimitforactionofthecosφalarm
canbeconfigured�
Itisactivatedeverytimethevalueofthecosφ
dropsbelowtheconfiguredvalueandthecurrent
ishigherthanprogrammed�
Thealarmmustbeenabled(5�19�- ENABLING
ALARMS”
Pressthe keytoentereditingmode�Itis
identifiedbythe symbolandtheblinkingof
thedigitstobemodified�
Inordertoavoidpossiblefalseactivationsofsaidalarms,theyhaveapredefineddelayof15
seconds�
Theparameterstobeconfiguredare:
Thecurrent value�
Thecos φ valueandwhetheritisinductiveLorcapacitiveC
The keyincreasesthedigitvalueorshowsthenextoption�
The keydecreasesthedigitvalueorshowsthenextoption�
The keyskipstothepreviousdigit�
The keyskipstothenextdigit�
Press tovalidatethedata;the symboldisappearsfromthedisplay
Current:
Maximum value: 9999A
Minimum value: 0A
cos φ:
Maximum value: 1�00
Minimum value: 0�80
Ifthevalueenteredislowerthantheminimumvalueorhigherthanthemaximumvalue,
thebacklightofthedisplayashesandthevalueenteredisreplacedwiththeminimumor
maximumvalue,orwiththelastvaluevalidated�
Pressthe keytoaccessthenextprogrammingstep�
Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,5�27�-
SIMULATION SCREEN